HOME / PRODUCTS / VRF System
ARV 5X Series
5 basic modules capacity range from 8~16HP

Full range capacity is from 8HP~ 64HP with 2HP increase.


High EER, up to EER 4.7


  • character
  • indoor unit
  • outdoor unit
 

Excellent In EER&COP                                                      Module Alternate Operation                  

ARV 5X Series achieves the industrys top                     In one combination system,any module could   

class energy efficiency in cooling and heating               run as the master unit according to the running

by utilizing all DC inverter in one system.                        time.Balance the life of the outdoor units

compressors, and high efficiency heat exchanger.             

The cooling EER is up to 4.67 and the heating

COP is up to 4.79 in the 8HP category.

                   

 

Long Piping Length                                                          Back-Up Operation Technology             

Because of using DC inverter control technology                      Module Back-Up Technology                    

and sub-cooling circuit technology ,it is possible                        As one of module breaks down, the rest of 

to design a system with longer piping and                               modules in the same refrigerant system start-up 

elevation difference which make it easier to                             urgently.

design and installation. 

 

                                                        

 

Auto Addressing                                                               6-Step Oil Separating Technology             

The outdoor units distribute indoor system                              Completely solve the problem of oil, the system 

address automatically. No need manually                                  more stable.  and reliable

setting. More convenient and saving the 

installation time.           

                                              

 

 

  

HP

8

10

12

14

16

Model

Outdoor

380~415V

ARV-H250/R1MX

ARV-H280/R1MX

ARV-H330/R1MX

ARV-H400/R1MX

ARV-H450/R1MX

220V

ARV-H250/9R1MX

ARV-H280/9R1MX

ARV-H330/9R1MX

ARV-H400/9R1MX

ARV-H450/9R1MX

Combination

HP

8

10

12

14

16

Capacity

Cooling

kW

25.2

28

33.5

40

45

Heating

kW

28.0

31.5

37.5

45

50

Electric Data

Power Supply

V~,Hz,Ph

380~415,50(60),3&220,60,3

Cooling Power Input

kW

5.40

7.00

8.40

10.50

12.40

Heating Power Input

kW

5.85

7.20

8.90

10.90

12.40

Cooling Current

A

8.60

10.80

13.50

18.20

20.30

Heating Current

A

8.75

10.95

13.80

16.50

19.00

EER

4.67

4.00

3.99

3.81

3.63

COP

4.79

4.38

4.21

4.13

4.03

Performance

Air Flow Volume

m3/h

12000

12000

12000

7250×2

7500×2

Noise Level

dB(A)

45-58

45-58

45-58

47-61

47-61

Compressor

Type

DC Inverter

DC Inverter

DC Inverter

DC Inverter

DC Inverter

Quantity

1

1

1

1

1

Fan Motor

Type

DC motor

DC motor

DC motor

DC motor

DC motor

Quantity

1

1

1

2

2

Max. No. of Indoor Units

unit

13

16

19

23

26

Connection Ratio

%

50~130

50~130

50~130

50~130

50~130

Dimension(WxDxH)

Net

mm

935×765×1600

935×765×1600

935×765×1600

1340×765×1600

1340×765×1600

Packing

mm

980×810×1850

980×810×1850

980×810×1850

1400×810×1850

1400×810×1850

Weight

Net

kg

223

223

248

298

298

Gross

kg

243

243

268

320

320

Refrigerant Type

R410a

R410a

R410a

R410a

R410a

Pipe Diameter

Liquid Side

mm(inch)

12.7(1/2)

12.7(1/2)

12.7(1/2)

12.7(1/2)

12.7(1/2)

Gas Side

mm(inch)

22.2(7/8)

22.2(7/8)

22.2(7/8)

28.6(9/8)

28.6(9/8)

Operation Range

Cooling

-15~52

-15~52

-15~52

-15~52

-15~52

Heating

-20~29

-20~29

-20~29

-20~29

-20~29

Stuffing Quantity

20/40/40H

unit

14/28/28

14/28/28

14/28/28

11/22/22

11/22/22

Copyright (C) 2016 China AUX Group Co.,Ltd. All Rights Deserved. 浙ICP备